CDU Installation Guide Page 30
Cooling Distribution Unit
OPERATION (continued)
Default 80 secs [adj. 1 to 300 secs] (time delay prior to pump low flow alarm)
Default 2 Bar [adj. 1 to 5 bar] (pump differential pressure set point when DOL)
Default 7 days [adj. 1 to 30 days] (pump/valve duty sharing period)
Default 03:00 hrs [adj. 00:00 to 23:59 hrs] (time of day for pump/valve duty
sharing change over)
Default 5 secs [adj. 1 to 10 secs] (dead time between pump change over)
Default 4 Bar [adj. 1 to 8 bar] (max pump speed control loop pressure)
Default 10 % [adj. 0 to 50 %] (set minimum pump speed)
6-2-12-1 Set point – Default 7.5 Bar [adj. 2 to 7.5 Bar]
6-2-12-2 Action – Default Alarm [adj. alarm only / shutdown]
6-2-13-1 Speed – Default 0 % [adj. 0 to 100 %] (initial start speed)
6-2-13-2 Period – Default 0 secs [adj. 0 to 30 secs] (delay prior to pump
speed DP loop becoming operational)
Default 1 [adj. 0 to 5] (no. of inverter restarts before fault recognition)
Default 18.0 °C [adj. 10 to 25 °C] (water supply temperature to racks)
Default 40 secs [adj. 10 to 180 secs] (valve motor run time for control loop)
Default Fixed SP + Dew Point override [adj. Fixed SP, Fixed SP + DW
O/R, DW tracking]
Default 2 °C [adj. 1 to 3 °C] (maintains set point threshold above dew point)
Default 5 secs [adj. 1 to 30 secs] (scan period for valve position control)
Default 10 % [adj. 0 to 50 %] (difference between demand & actual valve
position prior to alarm / change over)
Default 15 min [adj. 1 to 120 mins] (scan period for valve position monitoring)
6-3-8-1 Prop band – Default 17.0°C [adj. 1.0 to 25 °C]
6-3-8-2 Integral reset – Default 400 secs [adj. 0 to 999 secs]
Default 2.0 °C [adj. 1 to 10 °C] (temp. alarm threshold below set point)
Default 2.0 °C [adj. 1 to 10 °C] (temp. alarm threshold above set point)
Default 1.0 °C [adj. 0.5 to 5 °C] (low/high alarm reset threshold)
Default 20 °C [adj. 15 to 25 °C] (high alarm threshold when dew point
tracking)
Default 5 mins [adj. 1 to 30 mins] (time delay prior to alarm)
Default 4 °C [adj. 2 to 10 °C] (low temp. alarm threshold)
Default 11 °C [adj. 6 to 25 °C] (high temp. alarm threshold)
Default 1 °C [adj. 0.5 to 5 °C] (low/high temp. alarm reset threshold)
Default 0.6 Bar [adj. 0.2 to 1 Bar] (diff. pressure alarm threshold)
Default 0.2 Bar [adj. 0.1 to 0.5 Bar] (alarm reset threshold)
Default 60 secs [adj. 5 to 7200 secs] (time delay prior to alarm)
Default 0 °C [adj. +/-10 °C] (sensor calibration)
Default 0 °C [adj. +/-10 °C] (sensor calibration)
Default 0 °C [adj. +/-10 °C] (sensor calibration)
Default 0 °C [adj. +/-10 °C] (sensor calibration)
Default 0 % [adj. +/-10 %] (sensor calibration)
Default 0 Bar [adj. +/-1 Bar] (sensor calibration)
Default 0 Bar [adj. +/-1 Bar] (sensor calibration)
Default 0 Bar [adj. +/-1 Bar] (sensor calibration)
Default 0 Bar [adj. +/-1 Bar] (sensor calibration)
Default 15 min [adj. 1 to 120 mins] (time delay before system reverts to auto)
Default 20 min [adj. 1 to 120 mins] (alarm suppression on start up)
Default Alarm [adj. alarm only / shutdown] (unit flood tray sensor operation)